This is an AC power supply that converts DC power generated by photovoltaic panels into AC power, for reverse power flow, connected with the commercial grid. It uses the high frequency isolation method to isolate the photovoltaic cell and the commercial grid, allowing for safer operation and maintenance of photovoltaic cells. Moreover, since there is almost no flow of ground current due to stray capacitance from the photovoltaic cell, false operation of the earth leakage breaker is prevented.
Item Standard
Model PVS010T200 PVS010S200 PVS005T200
Method Inverter Voltage-current control (when interconnected)
Voltage-voltage control (Automatic)
Switching method High - Frequency PWM
Power control method Max. power tracking control
Isolation High-frequency isolation
Cooling Forced air cooling
DC input Rated input voltage DC320V
Operating input voltage range DC200~540V DC200~500V DC200~540V
MPPT operating range DC200~500V DC200~500V DC200~540V
Input circuits 7 circuits (10A/circuits) 4circuits(10A/circuits)
AC output Electrical type 3-phase 3-wire Single phase 3-wire 3-phase 3-wire
Rated voltage AC202V AC101V/202V AC202V
Rated frequency 50/60Hz
Rated output power 10kW 5kW
Output fundamental power-factor 0.95 or greater
Current distortion factor Total 5% or less 、3% or less each
Power conversion efficiency Including junction box function 93%
Excluding junction box function 93.90% 93.70% 93.60%
Independent operation detection Passive detection Voltage phase jump detection
Active detection Invalid power variation method
Autonomous AC output(optional) Electrical type Single phase 2-wire
Rated voltage AC100V
Rated frequency 3kW 1.5kW
System & Interconnection protection function Over Voltage Relay (OVR)/Under Voltage Relay(UVR)
Over Frequency Relay (OFR)/Under Frequency Relay (UFR) 
Other function Over voltage control function, external operation (OVGR, etc.,) function and measurement and monitoring function
Operation panel display Japanese
Dimensions (W)×(D)×(H)(mm) 600×260×600 600×260×700 600×260×475
Weight Less than 60kg Less than 63kg Less than 45kg
Environmental
specifications 
Usage location Indoor and outdoor
Ambient temperature -10~50℃
Humidity 10~90%RH


Many options available Abbreviated designation
No junction box type DN
Direct sunlight resistant SK
Many options available Abbreviated designation
Ground fault detecting module negative/positive terminals
Automatic operation SA



■Direct connection to low-voltage interconnection power distribution netoworks also possible.




Model PVS100T200-ID-DN-H1
Method Isolation type Commercial transformer isolation
Cooling type Forced air cooling
DC input Rate input voltage DC 345 V
Input operating voltage range DC325-600V
Maximum input Voltage DC 650V
Input circuits 2 circuits
AC output Electrical type 3-phase 3wire
Rated voltage AC 202V
Rated frequency 50/60 Hz
Rated output power 100 kW
Rated output current 286 A
Output fundamental power-factor 0.95 or greater
Maximum conversion efficiency 96.30%
Current distortion factor for each output Less than 3%
Independent operation detection Active detection Frequency shift method
System & Interconnection protection function Over Voltage Relay (OVR) / Under Voltage Relay (UVR)
Over Frequency Relay (OFR) / Under Frequency Relay (UFR)
Other function Monitor function (touch panel)
Dimensions (W)×(D)×(H) (mm) 800×950×1,900*
Weight Less than 1,200 kg
Communication function RS485 communication
Environmental specifications Usage location Indoor
Ambient temperature -5 to 40℃
Humidity 20 to 80% RH

*Not including base and ceiling protective covers