Location of Mount |
Indoors |
No salt damage, dust, or corrosive gases |
Surrounding Temperature |
5~40℃(continuous) 0~50℃(short time) |
- |
Relative Humidity |
5~85%(continuous) 5~90%(short time) |
Regardless, no condensation |
Item |
Units |
Rating/characteristic |
Notes |
||
Model |
Model Name |
- |
INV125VA |
||
Rating type |
- |
Continuous |
|||
Cooling method |
- |
Forced air cooling |
|||
DC Input |
Rated voltage |
V |
-48 |
||
Fluctuation range |
V |
-33~-57 |
|||
Max. input current |
A |
6 |
At rated output |
||
Input return noise |
mV |
Within 5 |
Rated input voltage, linear load |
||
AC Output |
Rated capacitance |
VA(W) |
125(125) |
Apparent power (effective power) (total output) |
|
No. of phases |
- |
Single-phase 2-wire |
|||
Rated voltage |
V |
100 |
Sine wave output |
||
Voltage set precision |
% |
Within±2 |
|||
Rated frequency |
Hz |
50/60 |
Manual switching (by setting switch) |
||
Frequency precision
|
% |
Within±1.0 |
|||
Waveform distortion |
Linear load |
% |
Within5 |
During rated operation |
|
Rectifier load |
% |
Within10 |
During rated operation |
||
Excess voltage fluctuation |
% |
Within±10 |
0⇔100% load change |
||
Set time |
ms |
Within150 |
|||
Load power factor |
- |
1.0 |
Fluctuation range 0.6 (lagging) ~ 1.0 |
||
Overcurrent protection |
% |
Within100 |
|||
High-Frequency Noise |
Conformant to VCCI-A |
||||
Acoustic Noise |
dB(A) |
Within50 |
When operating 1 unit, forward from unit 1m, A characteristic |
||

Location of Mount |
Indoors |
No salt damage, dust, or corrosive gases |
Surrounding Temperature |
5~40℃(continuous) 0~50℃(short time) |
- |
Relative Humidity |
5~85%(continuous) 5~90%(short time) |
Regardless, no condensation |
Item |
Units |
Rating/characteristic |
Notes |
||
Mode |
Model Name |
- |
INV1000SC |
||
Rating type |
- |
Continuous |
|||
Cooling method |
- |
Forced air cooling |
|||
DC Input |
Rated voltage |
V |
-48 |
||
Fluctuation range |
V |
-40.5~-57 |
|||
Max. input current |
A |
30 |
At rated output |
||
Input return noise |
mV |
Within2 |
Rated input voltage, linear load |
||
AC Output |
Rated capacitance |
kVA(kW) |
1.0(1.0) |
Parent power (effective power) (total output) |
|
No. of phases |
- |
Single-phase 2-wire |
|||
Rated voltage |
V |
100 |
Sine wave output |
||
Voltage set precision |
% |
Within±2 |
|||
Rated frequency |
Hz |
50/60 |
Manual switching (by setting switch) |
||
Frequency precision |
% |
Within±1.0 |
|||
Waveform distortion |
Linear load |
% |
Within5 |
During rated operation |
|
Rectifier load |
% |
Within8 |
During rated operation |
||
Excess voltage fluctuation |
% |
Within±10 |
0⇔100% load change |
||
Set time |
ms |
Within150 |
|||
Load power factor |
- |
0.9(lagging) |
Fluctuation range 0.6 (lagging) ~ 1.0 |
||
Overcurrent protection |
% |
105+ |
|||
High-Frequency Noise |
Conformant to VCCI-A |
||||
Acoustic Noise |
dB(A) |
Within55 |
When operating 1 unit, forward from unit 1m, A characteristic |
||
This AC power supply can supply high-quality and stable AC and is suited for datacom units such as routers and servers which demand high reliability (it may not be used otherwise than for communication units). It can be mounted to an EIA-standard or JIS-standard 19-inch rack.
A single-unit configuration allows a maximum of 1 kVA output. With a redundant configuration, 1 to 4 kVA output can be supported. A display unit can be embedded on an AC power unit that is not used as a single operator and display various states. Operational status signals, fault signals and overload state signals are output from the external signal terminal block, allowing one to monitor the unit's operational status.

Location of Mount |
Indoors |
No salt damage, dust, or corrosive gases |
Surrounding Temperature |
5~40℃(continuous) 0~50℃(short time) |
- |
Relative Humidity |
5~85%(continuous) 5~90%(short time) |
Regardless, no condensatio |
Item |
Units |
Rating/characteristic |
Notes |
||
Mode |
Model Name |
- |
E04HA1010D2R |
||
Rating type |
- |
Continuous |
|||
Cooling method |
- |
Forced air cooling |
|||
DC Input |
Rated voltage |
V |
-48 |
||
Fluctuation range |
V |
-40.5~-57 |
|||
Max. input current |
A |
29 |
At rated output |
||
Input return noise |
mV |
Within2 |
Rated input voltage, linear load |
||
AC Output |
Rated capacitance |
kVA(kW) |
1.0(1.0) |
Parent power (effective power) (total output) |
|
No. of phases |
- |
Single-phase 2-wire |
|||
Rated voltage |
V |
100 |
Sine wave output |
||
Voltage set precision |
% |
Within±2 |
|||
Rated frequency |
Hz |
50/60 |
Manual switching (by setting switch) |
||
Frequency precision |
% |
Within±1.0 |
|||
Waveform distortion |
Linear load |
% |
Within5 |
During rated operation |
|
Rectifier load |
% |
Within8 |
During rated operation |
||
Excess voltage fluctuation |
% |
Within±10 |
0⇔100% load change |
||
Set time |
ms |
Within150 |
|||
Load power factor |
- |
1.0 |
Fluctuation range 0.6 (lagging) to 1.0 |
||
Overcurrent protection |
% |
105+ |
|||
Power Conversion Efficiency |
% |
86+ |
At rated in/out, linear load, constant temp. |
||
High-Frequency Noise |
- |
Conformant to VCCI-A |
|||
Acoustic Noise |
dB(A) |
Within55 |
When operating 1 unit, forward from unit 1m, A characteristic |
||
Within65 |
In parallel redundant operation of 5 units |
||||
Item |
Units |
Rating/characteristic |
Notes |
||||
Model Name |
- |
INVSLF-S ・1000-S2 |
INVSLF-10 ・1000-S2 |
INVSLF-20 ・1000-S2 |
INVSLF-40 ・1000-S2 |
||
Max. Inverter Units |
- |
1 |
2 |
3 |
5 |
||
Display Unit |
- |
Yes |
Yes |
Yes |
Yes |
||
Rated Input capacitance |
A |
24 |
24 |
48 |
96 |
||
Rated Output Capacitance |
A |
29 |
29 |
58 |
116 |
Evaluation value (rated input voltage, linear load) |
|
AC Output |
Rated capacitance |
kVA (kW) |
1.0 (1.0) |
1.0 (1.0) |
2.0 (2.0) |
4.0 (4.0) |
Parent power (effective power) (total output) |
Rated voltage |
V |
100 |
Sine wave output |
||||
Voltage Settling Accuracy |
% |
Within± |
|||||
Load power factor |
- |
1.0 |
Fluctuation range 0.6 (lagging) ~ 1.0 |
||||